To generate finished foam from a water tender or a fixed installation without the need of a fixed foam proportioner. The inductors should be positioned such that there is about one meter of straight hose between water supply and the eductor and another meter of straight hose between eductor and the foam equipment.
Body and suction Coupling | Aluminium |
Metering device and control valve | Nylon |
Non-return ball | Polypropylene |
Screws and filter | Stainless steel |
Pick-up hose | PVC reinforced with a metal wire |
Suction rod | EPDM |
Maximum working pressure | 16 bar |
Maximum pressure | 25.5 bar |
Operating pressure at the inlet | 10 bar |
Operating pressure at the outlet | 6.5 bar |
Flow | 400 lpm |
Suction | Venturi, with no return valve |
Suction setting | By metering device 0%, 0.1%, 0.25%, 0.5%, 1%, 2%, 3%, 4%, 5% et 6% |
Pressure loss | 35% |
Type of foam agent recommended | All types of synthetic foams |
Weight | 2.6 Kg |
POK SAS
18 Cours Antoine Lavoisier | 10400 Nogent-sur-Seine | France
Contact Person: Amelien DRU, Commercial Manager, France
Sandeep Shrivastava, General Manager, India
Telephone : +33 (0) 37 49 53 - 272, +91 8510 828 702Email : [email protected], [email protected], [email protected]
Website :Click to visit website